GXT5-16KIRT9UXLE

Vertiv GXT5-16KIRT9UXLE UPS(Vertiv Liebert GXT5 1ph UPS, 16kVA)

التصنيفات: , Brand: EMERSON
الوصف

Technical Specifications 16-20 kVA

 

16KIRT9UXLE 20KIRT9UXLE
Ratings (VA/W) 16000 VA/16000 W 20000 VA/20000 W

Dimensions, inches (mm)

 

Unit W x D X H 16.9×24.8×15.5 16.9×24.8×15.5
(430×630×394) (430×630×394)
Unit 298 (135.2) 298 (135.2)

 

Operating Frequency, Nominal 50 or 60 Hz (factory-default is 50 Hz) 50 or 60 Hz (factory-default is 50 Hz)
Voltage Range 288 VAC 288 VAC
Input Wiring Input terminal block Input terminal block

 

Weight, pounds (kg) Input AC Parameters

Output AC Parameters

 

Output Receptacles Output terminal block Output terminal block
Factory-default VAC Frequency  

230 VAC, 50 Hz

 

230 VAC, 50 Hz

Waveform (On Battery) Sinewave Sinewave
Utility (AC) Mode Overload  

> 150% minimum 200 ms

 

> 150% minimum 200 ms

Battery

 

Type Valve-regulated, non-spillable, lead acid Valve-regulated, non-spillable, lead acid
Backup Time (100% Load) 3.5 Minutes 2.5 Minutes
Backup Time (50% Load) 9.5 Minutes 7 Minutes
+1 External Battery

Cabinet (100% Load)

10 Minutes 7 Minutes
+1 External Battery

Cabinet (50% Load)

26.5 Minutes 19.5 Minutes

Environmental Requirements

 

Operating Temperature,

°F (°C)

 

Storage Temperature,

°F (°C )

+32 to +104 (0 to 40) (no derating)

 

 

+5 to +104 (-15 to 40)

+32 to +104 (0 to 40) (no derating)

 

 

+5 to +104 (-15 to 40)

Relative Humidity Operating Elevation

 

Audible Noise

0% to 95%, non-condensing                                                                                0% to 95%, non-condensing

 

Up to 10,000 ft (3,000 m) at 77°F (25°C) without derating                                                  Up to 10,000 ft (3,000 m) at 77°F (25°C) without derating

 

 

<58 dBA, at 1 meter from the front                                                                          <58 dBA, at 1 meter from the front

Agency

 

Surge Immunity IEC/EN EN61000-4-5, Level 4, Criteria A; ANSI C62 41 Category B IEC/EN EN61000-4-5, Level 4, Criteria A; ANSI C62 41 Category B
Transportation ISTA Procedure 1E ISTA Procedure 1E
Safety UL1778, c-UL listed UL1778, c-UL listed
Emissions FCC Part 15 (Class A) FCC Part 15 (Class A)

Warranty

 

Std. 2 year; Opt. 1 and 3 year extension Std. 2 year; Opt. 1 and 3 year extension

 

External battery cabinets and replacement battery kits

 

UPS External battery cabinets Replacement battery kits
GXT5-5000IRT5UXLE GXT5-EBC192VRT3U GXT5-192VBATKIT (x 1pcs)
GXT5-6000IRT5UXLE GXT5-EBC192VRT3U GXT5-192VBATKIT (x 1pcs)
GXT5-8000IRT5UXLE GXT5-EBC192VRT3U GXT5-192VBATKIT (x 1pcs)
GXT5-10000IRT5UXLE GXT5-EBC192VRT3U GXT5-192VBATKIT (x 1pcs)
GXT5-16kRT9UXLE GXT5-EBC384VRT6U GXT5-384VBATKIT (x 1pcs)
GXT5-20kRT9UXLE GXT5-EBC384VRT6U GXT5-384VBATKIT (x 1pcs)

 

مراجعات (0)

المراجعات

لا توجد مراجعات بعد.

كن أول من يقيم “GXT5-16KIRT9UXLE”

لن يتم نشر عنوان بريدك الإلكتروني. الحقول الإلزامية مشار إليها بـ *

Shipping & Delivery

MAECENAS IACULIS

Vestibulum curae torquent diam diam commodo parturient penatibus nunc dui adipiscing convallis bulum parturient suspendisse parturient a.Parturient in parturient scelerisque nibh lectus quam a natoque adipiscing a vestibulum hendrerit et pharetra fames nunc natoque dui.

ADIPISCING CONVALLIS BULUM

  • Vestibulum penatibus nunc dui adipiscing convallis bulum parturient suspendisse.
  • Abitur parturient praesent lectus quam a natoque adipiscing a vestibulum hendre.
  • Diam parturient dictumst parturient scelerisque nibh lectus.

Scelerisque adipiscing bibendum sem vestibulum et in a a a purus lectus faucibus lobortis tincidunt purus lectus nisl class eros.Condimentum a et ullamcorper dictumst mus et tristique elementum nam inceptos hac parturient scelerisque vestibulum amet elit ut volutpat.